BAY AREA AIR QUALITY
MANAGEMENT DISTRICT |
Source Category
| Source: | Steam Generator - Oil field | Revision: | 3 |
| Document #: | 162.1.1 | ||
| Class: | >5 MMBtu/hr to < 33.5 MMbtu/hr Heat Input | Date: | 08/12/94 |
Determination
POLLUTANT |
BACT 1. Technologically Feasible/ Cost Effective 2. Achieved in Practice |
TYPICAL TECHNOLOGY |
| POC | 1. n/d 2. n/s |
1. n/d 2. Good Combustion Practicea |
| NOx | 1. n/d 2. 25 ppmv @ 3% O2 Drya |
1. n/d 2. Low NOx Burners + Flue Gas Recirculationa,b |
| SO2 | 1. n/d 2. Natural gas fuel or treated refinery gas w/ <100 ppmv total reduced sulfura |
1. n/d 2. Fuel Sectiona |
| CO | 1. n/d 2. 100 ppmv @ 3% O2 Drya |
1. n/d 2. Good Combustion Practicea |
| PM10 | 1. n/d 2. Natural gas fuel or treated refinery gas fuela |
1. n/d 2. Fuel Selectiona |
| NPOC | 1. n/a 2. n/a |
1. n/a 2. n/a |
References