BAY AREA AIR QUALITY
MANAGEMENT DISTRICT |
Source Category
| Source: | Steam Generator - Oil Field | Revision: | 3 |
| Document #: | 162.3.1 | ||
| Class: | >50 MMBtu/hr Heaat Input | Date: | 12/16/91 |
Determination
POLLUTANT |
BACT 1. Technologically Feasible/ Cost Effective 2. Achieved in Practice |
TYPICAL TECHNOLOGY |
| POC | 1. n/d 2. n/s |
1. n/d 2. Good Combustion Practicea |
| NOx | 1. 9 ppmv @ 3% O2
Drya 2. 25 ppmv @ 3% O2 Drya |
1. Selective catalytic
Reduction (SCR) + Low NOx Burners +
Flue Gas Recirculationa 2. Low NOx Burners + Flue Gas Recirculationa,b |
| SO2 | 1. n/d 2. Natural gas fuel or treated refinery gas w/ <100 ppmv total reduced sulfura |
1. n/d 2. Fuel Selectiona |
| CO | 1. 50 ppmv @ 3% O2
Drya 2. 100 ppmv @ 3% O2 Drya |
1. Good Combustion
Practice in Conjunction w/ Selective Catalytic Reduction (SCR) Systema 2. Good Combustion Practicea |
| PM10 | 1. n/d 2. Natural gas fuel or treated refinery gas fuela |
1. n/d 2. Fuel Selectiona |
| NPOC | 1. n/a 2. n/a |
1. n/a 2. n/a |
References