BAY AREA AIR QUALITY
MANAGEMENT DISTRICT |
Source Category
| Source: | Boiler, CO - Refinery | Revision: | 2 |
| Document #: | 17.4.1 | ||
| Class: | All | Date: | 04/21/93 |
Determination
POLLUTANT |
BACT 1. Technologically Feasible/ Cost Effective 2. Achieved in Practice |
TYPICAL TECHNOLOGY |
| POC | 1. n/d 2. n/s |
1. n/d 2. Minimum Furnace Gas bypassing + Good Comb ustion Practice c,d |
| NOx | 1. n/s 2. 80 ppm @ 3% O2, Drya |
1. Selective Catalytic
Reduction (SCR) + Flue Gas Recirculation + Technologies listed below c 2. Low NOx Burners + Reduced Air Preheat + Natural Gas or Treated Refinery Gas as Supplemental Fuel c,d |
| SO2 | 1. Natural gas or Treated
Refinery Gas Fuel w/ <50 ppm as hydrogen Sulfide as Supplemental Fuelc,d 2. Natural gas or Treated Refinery Gas Fuel w/ <100 PPm as hydrogen Sulfide as Supplemental Fuelc,d |
1. Fuel Selection a,d 2. Fuel Selection a,d |
| CO | 1. n/d 2. 100 ppm @ 3% O2, Dryc |
1. n/d 2. Minimum Furnace Gas Bypassing + Good Combustion Practicea,d |
| PM10 | 1. n/d 2. n/s |
1. n/d 2. Electrostatic Precipitatora |
| NPOC | 1. n/a 2. n/a |
1. n/a 2. n/a |
References
| a. SOHIO Refinery; Toledo, Ohio c. BAAQMD d. See also Catalyst Regeneration - Fluidized Catalytic Cracking Unit |