BAY AREA AIR QUALITY
MANAGEMENT DISTRICT |
Source Category
| Source: | Boiler or Water Heater - Landfill or Digester Gas | Revision: | 2 |
| Document #: | 17.5.1 | ||
| Class: | All | Date: | 04/21/93 |
Determination
POLLUTANT |
BACT 1. Technologically Feasible/ Cost Effective 2. Achieved in Practice |
TYPICAL TECHNOLOGY |
| POC | 1. n/d 2.Automatic combustion air control and retention time >0.3 sec. at >1600oF |
1. n/d 2. BAAQMD Approved Design and Operationb |
| NOx | 1. 20 ppm @ 3% O2,
Dryb 2. 40 ppm @ 3% O2, Dryb,c |
1. Selective Non-Catalytic
Reduction (SNCR ) Technologies listed belowb 2. Low NO2, Burners + Flue Gas Recirculation + Reduced Air Preheatb |
| SO2 | 1. n/s 2. n/d |
1.Spray Dryer + Baghouse; or
Fuel Gas Pretreatment Systema 2. n/d |
| CO | 1. n/d 2. 100 ppmv @ 3% O2 Dryb,c |
1. n/d 2. Good Combustion Practice in Minimal Gas Bypassing in Furnacea |
| PM10 | 1. n/s 2. n/s |
1. Baghouse or Electrostatic
Precipitator 2. Fuel Gas Filter |
| NPOC | 1. n/a 2. n/a |
1. n/a 2. n/a |
References
| b. BAAQMD c. County of Los Angeles Sanitation District |