BAY AREA
AIR QUALITY MANAGEMENT DISTRICT |
Source Category
| Source: | Gas Turbine | Revision: | 1 |
| Document #: | 89.1.5 | ||
| Class: | Combined Cycle (> = 2.0 MW and < 40 MW) | Date: | 07/18/03 |
Determination
POLLUTANT |
BACT 1. Technologically Feasible/ Cost Effective 2. Achieved in Practice |
TYPICAL TECHNOLOGY |
| POC | 1. n/d
2. 2.0 ppmv, Dry @ 15%O2 a,b |
1. n/d 2. Oxidation Catalyst a,b |
| NOx | 1. 2.5 ppmv, Dry @ 15%O2 a
(achieved in practice for >12 MW )a 2. 5.0 ppmv, Dry @ 15%O2 a,b |
1. SCR + Water or Steam Injection; or
SCONOx a 2. SCR + Water or Steam Injection a,b |
| SO2 | 1. Natural Gas Fuel a 2. Natural Gas Fuel a |
1. Fuel Selection
a 2. Fuel Selection a |
| CO | 1. n/d 2. 6.0 ppmv, Dry @15% O2 a,b |
1. n/d 2. Oxidation Catalyst a,b |
| PM10 | 1. Natural Gas Fuel
a 2. Natural Gas Fuel a,b |
1. Fuel Selection
a 2. Fuel Selection a,b |
| NPOC | 1. n/a 2. n/a |
1. n/a 2. n/a |
References
| a. Guidance for the Permitting of
Electrical Generation Technologies, CalEPA Air Resources Board,
Stationary Source Division, July 2002 b. Application #10962, UCSF Cogeneration Plant |