BAY AREA AIR QUALITY
MANAGEMENT DISTRICT |
Source Category
| Source: | Hazardous Waste Incineration | Revision: | 1 |
| Document #: | 93.1 | ||
| Class: | All | Date: | 10/25/91 |
Determination
POLLUTANT |
BACT 1. Technologically Feasible/ Cost Effective 2. Achieved in Practice |
TYPICAL TECHNOLOGY |
| POC | 1. n/d 2. Automatic combustion air control, >2 sec. retention time and >1800oF exit temperaturea |
1. n/d 2. BAAQMD Approved Design and Operationb |
| NOx | 1. n/d 2. n/s |
1. n/d 2. Natural Gas Supplemental Fuel with Selective Non-Catalytic Reductiona |
| SO2 | 1. n/d 2. n/s |
1. n/d 2. Natural Gas Supplemental Fuel with Selective Non-Catalytic Reductiona |
| CO | 1. n/d 2. Automatic combustion air control, >2 sec. retention time and >1800oF exit temperaturea |
1. n/d 2. BAAQMD Approved Design and Operationb |
| PM10 | 1. n/d 2. <0.002 gr/dscf @ 12% CO2a |
1. n/d 2. Baghouseb |
| NPOC | 1. n/a 2. n/a |
1. n/a 2. n/a |
References
| a. SCAQMD Guideline b. BAAQMD |